{"title":"DALI \u0026 DALI-2 Lighting Control Cable","description":"\u003cp\u003eShop DALI and DALI-2 lighting-control bus cable options for commercial and residential lighting systems. DALI uses a polarity-insensitive two-wire bus that carries both communication and bus power on the same adjacent pair.\u003c\/p\u003e\n\u003ch2\u003eChoosing DALI Control Cable\u003c\/h2\u003e\n\u003cp\u003eThe DALI Alliance recommends standard 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. Use 14 AWG for the strongest long-run option in this collection. Use 16 AWG or 18 AWG only where the system designer confirms the run length, bus current, voltage drop, and terminal capacity.\u003c\/p\u003e\n\u003cp\u003eRiser and plenum options are available. These bulk cables are suitable for DALI bus applications but are not DALI-2 certified control devices. Verify the required jacket rating, installation method, separation from mains wiring, and all local electrical-code requirements before installation.\u003c\/p\u003e\n\u003cp\u003e\u003ca href=\"\/blogs\/product-guides\/dali-cable-guide-wire-gauge-distance-plenum-riser\"\u003e\u003cstrong\u003eRead the complete DALI Cable Guide\u003c\/strong\u003e\u003c\/a\u003e for the wire-gauge table, maximum distances, stranded-conductor guidance, and the 14-2C-P-WHT voltage-drop calculation.\u003c\/p\u003e","products":[{"product_id":"14-2c-blk","title":"14-2C-BLK Black Commercial grade general purpose 14 AWG 2 conductor cable","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003cp\u003e* Stranded Annealed Bare Copper Conductors|\u003cbr\u003e* Semi-Rigid PVC Insulation|\u003cbr\u003e* Twisted, unshielded|\u003cbr\u003e* Riser rated PVC Jacket|\u003cbr\u003e* NEC CL3R, CEC CMG, RoHS Compliant|\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis 14 AWG, 2-conductor cable is a practical option for DALI and DALI-2 lighting-control bus wiring when its CL3R\/CMG riser-rated rating, conductor size, run length, and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 14 AWG cable provides greater conductor area than that recommendation, but the system designer must still confirm distance, voltage drop, terminal capacity, and installation method.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CL3R\/CMG riser-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":8468544061483,"sku":"14-2C-BLK","price":539.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/14-2C-BLK.png?v=1601398375"},{"product_id":"14-2c-gry","title":"14-2C-GRY Grey Commercial grade general purpose 14 AWG 2 conductor cable","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003cp\u003e* Stranded Annealed Bare Copper Conductors|\u003cbr\u003e* Semi-Rigid PVC Insulation|\u003cbr\u003e* Twisted, unshielded|\u003cbr\u003e* Riser rated PVC Jacket|\u003cbr\u003e* NEC CL3R, CEC CMG, RoHS Compliant|\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis 14 AWG, 2-conductor cable is a practical option for DALI and DALI-2 lighting-control bus wiring when its CL3R\/CMG rating and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 14 AWG cable provides greater conductor area, but the system designer must still confirm distance, voltage drop, terminal capacity, and installation method.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify riser, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":8468548747307,"sku":"14-2C-GRY","price":539.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/14-2C-GRY.png?v=1601398377"},{"product_id":"14-2c-p-blk","title":"14-2C-P-BLK Black Commercial grade general purpose 14 AWG 2 conductor plenum cable","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003cp\u003e* Stranded Annealed Bare Copper Conductors|\u003cbr\u003e* Plenum rated PVC Alloy insulation|\u003cbr\u003e* Twisted, unshielded|\u003cbr\u003e* Plenum rated PVC Jacket|\u003cbr\u003e* NEC CL3P, CEC CMP FT6, RoHS Compliant|\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis 14 AWG, 2-conductor cable is a practical option for DALI and DALI-2 lighting-control bus wiring when its CL3P plenum-rated rating, conductor size, run length, and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 14 AWG cable provides greater conductor area than that recommendation, but the system designer must still confirm distance, voltage drop, terminal capacity, and installation method.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CL3P plenum-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":8468558118955,"sku":"14-2C-P-BLK","price":544.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/14-2C-P-BLK.jpg?v=1601398380"},{"product_id":"14-2c-p-wht","title":"Liberty 14-2C-P-WHT 14 AWG plenum speaker cable white","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003ch3\u003e1000 ft spool of Liberty Wire \u0026amp; Cable (LWC) 14-2C-P-WHT\u003c\/h3\u003e\u003ch3\u003eFeatures and Benefits\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003e14 AWG Stranded Annealed Bare Copper Conductors\u003c\/li\u003e\n\u003cli\u003e2 Conductor\u003c\/li\u003e\n\u003cli\u003ePlenum rated PVC Alloy insulation\u003c\/li\u003e\n\u003cli\u003eTwisted, unshielded\u003c\/li\u003e\n\u003cli\u003ePlenum rated PVC Jacket\u003c\/li\u003e\n\u003cli\u003eNEC CL3P, CEC CMP FT6, RoHS Compliant\u003c\/li\u003e\n\u003cli\u003eWhite\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003e14-2C-P-WHT Applications\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003eSpeaker Level Audio Distribution\u003c\/li\u003e\n\u003cli\u003e70V Speaker systems\u003c\/li\u003e\n\u003cli\u003eDC Power, Class 2 and Class 3 power, system control\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003e14-2C-P-WHT is comparable to:\u003c\/h4\u003e\u003ctable id=\"cross_table\" class=\"responsive-table ui-responsive table table-bordered product-table ui-table ui-table-reflow mce-item-table\" data-role=\"table\" data-mode=\"reflow\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth width=\"30%\"\u003eManufacturer\u003c\/th\u003e\n\u003cth\u003ePart Number\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eExtron\u003c\/td\u003e\n\u003ctd\u003e22-155-03\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWest Penn\u003c\/td\u003e\n\u003ctd\u003e25226\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWest Penn\u003c\/td\u003e\n\u003ctd\u003e25226B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWindy City\u003c\/td\u003e\n\u003ctd\u003e447960S\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden\u003c\/td\u003e\n\u003ctd\u003e6100UE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden NG\u003c\/td\u003e\n\u003ctd\u003e6100UE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGepco\u003c\/td\u003e\n\u003ctd\u003eSSU142P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\u003cp\u003e\u003cbr data-mce-bogus=\"1\"\u003e\u003c\/p\u003e\u003cp\u003e\u003cspan style=\"text-decoration: underline;\" data-mce-style=\"text-decoration: underline;\"\u003e\u003cstrong\u003eContractors contact us for wholesale pricing\u003c\/strong\u003e\u003c\/span\u003e\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis 14 AWG, 2-conductor cable is a practical option for DALI and DALI-2 lighting-control bus wiring when its CL3P plenum-rated rating, conductor size, run length, and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 14 AWG cable provides greater conductor area than that recommendation, but the system designer must still confirm distance, voltage drop, terminal capacity, and installation method.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CL3P plenum-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":8468558479403,"sku":"14-2C-P-WHT","price":544.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/14-2C-P-WHT.png?v=1601398381"},{"product_id":"16-2c-blk","title":"16-2C-BLK Black Commercial grade general purpose 16 AWG 2 conductor cable","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003cp\u003e* 19-Strand Annealed Bare Copper Conductors|\u003cbr\u003e* Semi-Rigid PVC Insulation|\u003cbr\u003e* Twisted, unshielded|\u003cbr\u003e* Riser rated PVC Jacket|\u003cbr\u003e* NEC CL3R, CEC CMG, RoHS Compliant|\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis 16 AWG, 2-conductor cable is a practical option for DALI and DALI-2 lighting-control bus wiring when its CMR riser-rated rating, conductor size, run length, and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 16 AWG cable is slightly smaller than the recommended 1.5 mm² conductor, so full-distance use should be confirmed by the system designer based on bus current and voltage drop.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CMR riser-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":8468565262379,"sku":"16-2C-BLK","price":308.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/16-2C-GRY.png?v=1601398422"},{"product_id":"16-2c-gry","title":"16-2C-GRY Grey Commercial grade general purpose 16 AWG 2 conductor cable","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003cp\u003e* 19-Strand Annealed Bare Copper Conductors|\u003cbr\u003e* Semi-Rigid PVC Insulation|\u003cbr\u003e* Twisted, unshielded|\u003cbr\u003e* Riser rated PVC Jacket|\u003cbr\u003e* NEC CL3R, CEC CMG, RoHS Compliant|\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis 16 AWG, 2-conductor cable is a practical option for DALI and DALI-2 lighting-control bus wiring when its CMR riser-rated rating, conductor size, run length, and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 16 AWG cable is slightly smaller than the recommended 1.5 mm² conductor, so full-distance use should be confirmed by the system designer based on bus current and voltage drop.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CMR riser-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":8468573519915,"sku":"16-2C-GRY","price":308.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/16-2C-GRY_47cecf8e-60fe-4397-a661-55885661f019.png?v=1601398425"},{"product_id":"16-2c-p-blk","title":"Liberty 16-2C-P-BLK 16 AWG 2C plenum cable in black","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003ch2\u003e1000 ft of Liberty Wire \u0026amp; Cable Part no. 16-2C-P-BLK - Plenum 16 gauge 2 conductor Speaker Cable in Black\u003c\/h2\u003e\u003ch4\u003eFeatures and Benefits\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003eStranded Annealed Bare Copper Conductors\u003c\/li\u003e\n\u003cli\u003ePlenum rated PVC Alloy insulation\u003c\/li\u003e\n\u003cli\u003eTwisted, unshielded\u003c\/li\u003e\n\u003cli\u003ePlenum rated PVC Jacket\u003c\/li\u003e\n\u003cli\u003eNEC CMP, CEC CMP FT6, RoHS Compliant\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003eApplications\u003c\/h4\u003e\u003cul\u003e\n\u003cli\u003eSpeaker Level Audio Distribution\u003c\/li\u003e\n\u003cli\u003e70V Speaker systems\u003c\/li\u003e\n\u003cli\u003eDC Power, Class 2 and Class 3 power, system control\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003e16-2C-P-BLK is comparable to:\u003c\/h4\u003e\u003ctable id=\"cross_table\" class=\"responsive-table ui-responsive table table-bordered product-table ui-table ui-table-reflow mce-item-table\" data-role=\"table\" data-mode=\"reflow\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth width=\"30%\"\u003eManufacturer\u003c\/th\u003e\n\u003cth\u003ePart Number\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eWindy City\u003c\/td\u003e\n\u003ctd\u003e0013670S\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExtron\u003c\/td\u003e\n\u003ctd\u003e22-154-03\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWest Penn\u003c\/td\u003e\n\u003ctd\u003e25225B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden\u003c\/td\u003e\n\u003ctd\u003e6200FE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden\u003c\/td\u003e\n\u003ctd\u003e6200UE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden NG\u003c\/td\u003e\n\u003ctd\u003e6200UE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWindy City\u003c\/td\u003e\n\u003ctd\u003e916021911S\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGepco\u003c\/td\u003e\n\u003ctd\u003eSSU162P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden\u003c\/td\u003e\n\u003ctd\u003eZ133138B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\u003cp\u003e\u003cbr data-mce-bogus=\"1\"\u003e\u003c\/p\u003e\u003cp\u003e\u003cspan style=\"text-decoration: underline;\" data-mce-style=\"text-decoration: underline;\"\u003e\u003cstrong\u003eContractors - Contact Us for wholesale pricing on 16-2C-P-BLK\u003cbr\u003e\u003c\/strong\u003e\u003c\/span\u003e\u003c\/p\u003e\u003cp\u003e\u003cbr data-mce-bogus=\"1\"\u003e\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis 16 AWG, 2-conductor cable is a practical option for DALI and DALI-2 lighting-control bus wiring when its CMP plenum-rated rating, conductor size, run length, and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 16 AWG cable is slightly smaller than the recommended 1.5 mm² conductor, so full-distance use should be confirmed by the system designer based on bus current and voltage drop.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CMP plenum-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":8468576370731,"sku":"16-2C-P-BLK","price":335.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/16-2C-P-BLK.png?v=1601398431"},{"product_id":"16-2c-p-wht","title":"Liberty 16 AWG 2 conductor plenum cable white - 16-2C-P-WHT","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003ch2\u003e1000 ft of Liberty Wire \u0026amp; Cable Plenum 16 gauge 2 conductor Speaker Cable in White\u003c\/h2\u003e\u003ch3\u003e16-2C-P-WHT Features and Benefits\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eStranded Annealed Bare Copper Conductors\u003c\/li\u003e\n\u003cli\u003ePlenum rated PVC Alloy insulation\u003c\/li\u003e\n\u003cli\u003eTwisted, unshielded\u003c\/li\u003e\n\u003cli\u003ePlenum rated PVC Jacket\u003c\/li\u003e\n\u003cli\u003eNEC CMP, CEC CMP FT6, RoHS Compliant\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003e16-2C-P-WHT Applications\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eSpeaker Level Audio Distribution\u003c\/li\u003e\n\u003cli\u003e70V Speaker systems\u003c\/li\u003e\n\u003cli\u003eDC Power, Class 2 and Class 3 power, system control\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch4\u003e16-2C-P-WHT is comparable to:\u003c\/h4\u003e\u003ctable id=\"cross_table\" class=\"responsive-table ui-responsive table table-bordered product-table ui-table ui-table-reflow mce-item-table\" data-role=\"table\" data-mode=\"reflow\"\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth width=\"30%\"\u003eManufacturer\u003c\/th\u003e\n\u003cth\u003ePart Number\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eWindy City\u003c\/td\u003e\n\u003ctd\u003e001360S\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExtron\u003c\/td\u003e\n\u003ctd\u003e22-154-03\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWest Penn\u003c\/td\u003e\n\u003ctd\u003e25225\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWest Penn\u003c\/td\u003e\n\u003ctd\u003e25225B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden\u003c\/td\u003e\n\u003ctd\u003e6200FE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden\u003c\/td\u003e\n\u003ctd\u003e6200UE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden NG\u003c\/td\u003e\n\u003ctd\u003e6200UE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWindy City\u003c\/td\u003e\n\u003ctd\u003e991360S\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGepco\u003c\/td\u003e\n\u003ctd\u003eSSU162P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBelden\u003c\/td\u003e\n\u003ctd\u003eZ133138B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\u003cp\u003e\u003cbr data-mce-bogus=\"1\"\u003e\u003c\/p\u003e\u003cp\u003e\u003cspan style=\"text-decoration: underline;\" data-mce-style=\"text-decoration: underline;\"\u003e\u003cstrong\u003eContractors Contact Us for Wholesale Pricing\u003c\/strong\u003e\u003c\/span\u003e\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis 16 AWG, 2-conductor cable is a practical option for DALI and DALI-2 lighting-control bus wiring when its CMP plenum-rated rating, conductor size, run length, and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 16 AWG cable is slightly smaller than the recommended 1.5 mm² conductor, so full-distance use should be confirmed by the system designer based on bus current and voltage drop.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CMP plenum-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":8468576632875,"sku":"16-2C-P-WHT","price":335.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/16-2C-P-WHT.png?v=1601398433"},{"product_id":"liberty-18-2c-vpp-wht-500","title":"Liberty 18-2C-VPP-WHT Plenum 0-10V Dimmer Cable – 500 ft","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003ch2\u003e\u003cstrong\u003e500 ft spool of Liberty Wire \u0026amp; Cable (LWC) 18-2C-VPP-WHT\u003c\/strong\u003e\u003c\/h2\u003e\u003cp\u003eOEM Lighting Systems support cable for 0-10V LED Ballasts\u003c\/p\u003e\u003ch3\u003e\u003cstrong\u003e18-2C-VPP-WHT Features and Benefits\u003c\/strong\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eNEC required Violet \u0026amp; Pink insulation color code\u003c\/li\u003e\n\u003cli\u003eSolid annealed bare copper conductors\u003c\/li\u003e\n\u003cli\u003ePlenum rated PVC alloy insulation\u003c\/li\u003e\n\u003cli\u003eTwisted, unshielded\u003c\/li\u003e\n\u003cli\u003ePlenum rated PVC jacket\u003c\/li\u003e\n\u003cli\u003eNEC CMP, CEC FT6, RoHS compliant\u003c\/li\u003e\n\u003cli\u003e500 foot spools\u003c\/li\u003e\n\u003cli\u003eBetter than Belden 2285P\u003c\/li\u003e\n\u003cli\u003eLimit to 300 ft cable runs (\u003ca href=\"https:\/\/rf-av.com\/products\/16-2c-lvbp-wht\" data-mce-href=\"https:\/\/rf-av.com\/products\/16-2c-lvbp-wht\"\u003euse 16 AWG for longer runs\u003c\/a\u003e)\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003e\u003cstrong\u003e18-2C-VPP-WHT Applications\u003c\/strong\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003ePlenum Low Voltage 0-10V Ballast wiring and connection\u003c\/li\u003e\n\u003cli\u003ePlenum Low Voltage Security and Control\u003c\/li\u003e\n\u003cli\u003ePlenum DC Power, Class 2 and Class 3 power\u003c\/li\u003e\n\u003cli\u003ePlenum Rated Light Dimmer Cable\u003c\/li\u003e\n\u003c\/ul\u003e\u003cul\u003e\u003c\/ul\u003e\u003ch3\u003eNeed a Shorter Length?\u003c\/h3\u003e\u003cp\u003e\u003ca href=\"https:\/\/rf-av.com\/products\/by-the-foot-liberty-18-2c-VPP\" title=\"by the foot 18-2c-vpp\" data-mce-href=\"https:\/\/rf-av.com\/products\/by-the-foot-liberty-18-2c-VPP\"\u003eGet \u003cspan data-mce-fragment=\"1\"\u003e0-10V ballast wiring by the Foot at $0.49 \/ ft\u003c\/span\u003e\u003c\/a\u003e\u003c\/p\u003e\u003cp class=\"Ld6Rm\"\u003e\u003ca href=\"https:\/\/rf-av.com\/products\/by-the-foot-liberty-18-2c-VPP\" title=\"by the foot 18-2c-vpp\" data-mce-href=\"https:\/\/rf-av.com\/products\/by-the-foot-liberty-18-2c-VPP\"\u003e\u003cspan\u003ehttps:\/\/rf-av.com\/products\/by-the-foot-liberty-18-2c-VPP\u003c\/span\u003e\u003c\/a\u003e\u003c\/p\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis solid 18 AWG, 2-conductor 0-10V control cable can also be used for appropriately sized DALI and DALI-2 lighting-control bus wiring when its CMP plenum-rated rating and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 18 AWG cable is smaller than the recommended 1.5 mm² conductor and should be used only for appropriately shorter DALI runs; retain the product’s existing 300 ft guidance unless the system designer approves otherwise.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CMP plenum-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":39830582689873,"sku":"18-2c-vpp-wht-500","price":208.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/products\/closeup.png?v=1648064188"},{"product_id":"liberty-18-2c-vp-gry-0-10v-dimmer-cable-cmr-1000-ft","title":"Liberty 18-2C-VP-GRY 0-10V Dimmer Cable CMR - 1000 ft","description":"\u003cdiv class=\"rfav-availability-note\"\u003e\u003cp\u003e\u003cstrong\u003eAvailability note:\u003c\/strong\u003e Availability is subject to current manufacturer stock. For time-sensitive projects, call RF-AV at (800) 239-0312 for current lead time before ordering.\u003c\/p\u003e\u003c\/div\u003e\u003ch2 data-mce-fragment=\"1\"\u003e1000 ft spool of Liberty Wire \u0026amp; Cable Dimming Ballast Cable Non-Plenum Riser Rated\u003c\/h2\u003e\u003cp data-mce-fragment=\"1\"\u003e\u003cspan data-mce-fragment=\"1\"\u003eGrey OEM Lighting Systems Support Cable for 0-10V LED Ballasts Reel\u003c\/span\u003e - Non-Plenum\u003c\/p\u003e\u003ch3 data-mce-fragment=\"1\"\u003eLiberty 18-2C-VP-GRY Features and Benefits\u003c\/h3\u003e\u003cul data-mce-fragment=\"1\"\u003e\n\u003cli data-mce-fragment=\"1\"\u003e2022 NEMA Special color code matching the ballast leads (Violet\/Purple and Pink)\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eSolid annealed bare copper conductors\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003ePVC insulation\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eTwisted, unshielded\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eRiser rated PVC jacket\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eNEC CMR, CEC FT4, RoHS compliant\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003e1000 foot spools\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eSequential Foot Markers for cable run distance\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eBetter than Belden 2285R\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eLimit to 300 ft runs (\u003ca title=\"16 AWG Ballast Cable\" href=\"https:\/\/rf-av.com\/products\/16-2c-lvb-gry\" data-mce-fragment=\"1\" data-mce-href=\"https:\/\/rf-av.com\/products\/16-2c-lvb-gry\"\u003eUse 16 AWG for longer runs\u003c\/a\u003e)\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3 data-mce-fragment=\"1\"\u003e\n\u003cspan data-mce-fragment=\"1\"\u003eLiberty 18-2C-VP-GRY \u003c\/span\u003eApplications\u003c\/h3\u003e\u003cul data-mce-fragment=\"1\"\u003e\n\u003cli data-mce-fragment=\"1\"\u003eLow voltage 0-10V ballast wiring and connection\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eLow voltage security and control\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eDC power, class 2 and class 3 power\u003c\/li\u003e\n\u003cli data-mce-fragment=\"1\"\u003eNon-Plenum Rated Light Dimmer Cable\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eDALI and DALI-2 Lighting Control Bus Cable\u003c\/h2\u003e\u003cp\u003eThis solid 18 AWG, 2-conductor 0-10V control cable can also be used for appropriately sized DALI and DALI-2 lighting-control bus wiring when its CMR riser-rated rating and installation method meet the project requirements and local electrical code. DALI carries bus power and digital communication on one adjacent pair, and the bus connection is polarity-insensitive.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eRun-length guidance:\u003c\/strong\u003e The DALI Alliance recommends 1.5 mm² (15 AWG) two-core cable for up to 300 m (984 ft) between the two farthest devices at the maximum 250 mA bus current. This 18 AWG cable is smaller than the recommended 1.5 mm² conductor and should be used only for appropriately shorter DALI runs; retain the product’s existing 300 ft guidance unless the system designer approves otherwise.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eImportant:\u003c\/strong\u003e This is bulk cable suitable for DALI bus applications; it is not a DALI-2 certified control device. Use it for the control bus, not branch-circuit power. Verify CMR riser-rated, raceway, separation, and local-code requirements, especially near mains wiring.\u003c\/p\u003e","brand":"Liberty AV Solutions","offers":[{"title":"Default Title","offer_id":46958405320988,"sku":"","price":357.66,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/2702\/0014\/files\/cablecloseup_36c7b92d-18fe-4032-84c2-2ca2919eca0b.png?v=1696442274"}],"url":"https:\/\/rf-av.com\/collections\/dali-dali-2-lighting-control-cable.oembed","provider":"RF-AV","version":"1.0","type":"link"}